8. Electric connection
The polarity of T1, T2 and T3 temperature sensors is not
important. When connecting ULTRAFLOW
®
and electronic
sensor units, use the colours given for V1 and V2 flow meters.
Flow meters with Reed-contact output need to be connected to
clips 11-10, or 11-69.
V1 V2
- 11 11 Blue
+ 9 9 Red
SIG 10 69 Yellow
Clip
number
Standard heat and cold
measurements
Heat measurement
and leak records
Energy
measurement in
open systems
T1 5-6 Sensor in supply piping
(red)
Sensor in supply
piping (red)
Sensor in supply
piping (red)
T2 7-8 Sensor in return piping
(blue)
Sensor in return
piping (blue)
Sensor in return
piping (blue)
V1 11-9-10 Flow meter in supply or
return piping
Flow meter in supply
piping
Flow meter in
supply piping
V2 11-9-69 - Flow meter in return
piping
Flow meter in
return piping
T3 51-52 - Container/heat
exchanger
temperature
Reference sensor
(grey)
9. Insert modules
MULTICAL
®
601 can be extended with a range of functions, using the insert
modules. Individual modules are briefly described below.
9.1 Data/impulse inputs
Data outputs are used, for example, for
computer connection. The signal is passive and
galvanic ally separated using opto-electric
coupling elements. Transmission to RS232
level requires a connection of data cable 66-99-
106 (D-Sub 9F) or 66-99-098 (USB), through
the following connection:
62 Brown (DAT)
63 White (REQ)
64 Green (GND)