1. General information
Before installing the power meter, study this guide carefully. In case the meter is
not properly installed, the Kamstrup Company withdraws all its warranty
commitments.
Please, notice that it is necessary to meet the following installation conditions:
- ULTRAFLOW
®
compression stage: PN16/PN25/PN40, see the ;
labelling. The flow meter labelling
does not concern the accessories
supplied.
- Kamstrup compression stage
of DS temperature sensors: PN16
- The compression stage of stainless
steel containers: PN25/PN40 – according to the type
If the medium temperature exceeds 90°C, we recommend using flange meters, and
mounting the MULTICAL
®
601 on a wall.
2. Temperature sensor assembly
Temperature sensors used for measuring supply and return temperatures form a
pair; they must never be separated form each other.
MULTICAL
®
601 is usually supplied with mounted temperature sensors. According to
the EN 1434 and OIML R75 standards, their cable length must not be changed. If the
sensors need to be exchanged, the complete pair must always be replaced.
The red marked sensor must be placed in the supply piping. The other sensor has a
blue marking, and must be mounted into the return piping.
2.1 Container sensors
It is best to mount the container sensors into T-shaped branches or 45° Y-branches.
The end of the container must be placed in the direction of flow, and in the centre of
water flow.